401 Single display controller
Available Configuration
Output 1
Output 2
Output 3 / CT Input
Power supply
Description
Microprocessor controller in 48x48 mm (1/16 DIN) format, manufactured with SMT technology.
This instrument offers a full operator interface protected by a Lexan® membrane providing IP65 frontal protection. It includes 4 keys, a 4-digit display, 2 indicator LEDs for model 400, 3 LEDs for model 401, plus an additional 3-segment LED bar graph.
The main process input is universal and supports multiple sensor types:
- Thermocouples: J, K, R, S, T, B, E, N
- 3-wire PT100 resistance thermometers
- PTC thermistors
- Linear inputs: 0–60 mV, 12–60 mV, 0–20 mA, 4–20 mA, 0–10 V, 2–10 V
Input type is selected from the front panel; no external shunts or adapters are needed.
Model 401 provides an auxiliary input for a 50 mA AC current transformer to monitor load current, with the option to set an alarm for potential load faults.
Outputs include 2 (or 3 for model 401) relay outputs (5 A / 250 VAC, cosφ=1) or static outputs (10 Vdc / 30 mA) configurable for Heat, Cool, or combined Heat/Cool operation and/or alarm signaling.
Programming is organized in function blocks (CFG for control, Inp for inputs, Out for outputs, etc.) with a simplified menu for commonly used parameters.
A PC programming kit is available, including a menu-driven Windows configuration tool and connection cable (see technical data cod. 80021).
Optional password protection can restrict parameter viewing and editing.
- Universal input configurable directly from the front panel
- Accuracy better than 0.2% F.S. under nominal conditions
- Deviation indicated via LED bargraph
- Control output: relay or logic with Heat/Cool functionality
- One configurable alarm with up to 3 setpoints
- Self-tuning, auto-tuning, soft-start, manual/auto transfer
- Configurable via serial communication line
- Optional auxiliary input for 50 mA AC current transformer or third alarm output (relay or logic) for model 401